title: Explorador de capacidad de IA en datacenters
description: Dimensiona aceleradores y cómputo de IA a partir de potencia de instalación, PUE, racks, refrigeración, densidad, TDP y MFU sin derivar throughput de inferencia desde FLOPs.
hide:
  - toc
  - navigation
  - footer
---

<link rel="stylesheet" href="/stylesheets/tools.css" />
<link rel="stylesheet" href="/stylesheets/tools-datacenter-capacity.css" />
<script src="/assets/javascripts/tools/datacenter-ai-capacity-core.js" defer></script>
<script src="/assets/javascripts/tools/datacenter-ai-capacity.js" defer></script>
<script type="application/ld+json">{"@context":"https://schema.org","@type":"WebApplication","name":"Explorador de capacidad de IA en datacenters — 5sigmas","url":"https://5sigmas.com/herramientas/capacidad-datacenter-ia/","applicationCategory":"EducationalApplication","operatingSystem":"Any","isAccessibleForFree":true,"description":"Explorador interactivo para separar límites de potencia total, potencia por rack, refrigeración, densidad física y capacidad de cómputo de un datacenter de IA."}</script>

<div class="s5-landing s5-tool-page s5-datacenter-capacity" data-s5-datacenter-ai-capacity data-locale="es">
<section class="s5-page-intro">
  <div class="s5-eyebrow">Herramientas · Infraestructura · 17</div>
  <h1>Encuentra qué limita la capacidad real de un datacenter de IA.</h1>
  <p>Define la potencia total de la instalación, el PUE, los racks, la densidad y la refrigeración. El explorador calcula cuántos aceleradores pueden estar activos y mantiene separado el límite físico del rendimiento de entrenamiento y del throughput de inferencia.</p>
</section>
<div class="s5-tool-summary-strip"><div><small>Instalación</small><strong>MW totales → IT</strong></div><div><small>Rack</small><strong>potencia + refrigeración</strong></div><div><small>Entrenamiento</small><strong>pico × MFU</strong></div><div><small>Inferencia</small><strong>solo desde medición</strong></div></div>

<div class="s5-tool-workbench">
<form class="s5-tool-controls" aria-label="Supuestos del datacenter" onsubmit="return false">
<section class="s5-tool-controls__section"><h2>Instalación</h2><div class="s5-tool-field"><label for="s5-dc-fac-es">Potencia total de instalación <span>MW</span></label><input id="s5-dc-fac-es" data-field="facilityMW" type="number" min="0.01" step="0.5" value="10" inputmode="decimal" /><small>Incluye IT y soporte de instalación. El presupuesto IT se deriva con el PUE representativo.</small></div><div class="s5-tool-field"><label for="s5-dc-pue-es">PUE representativo</label><input id="s5-dc-pue-es" data-field="pue" type="number" min="1" max="5" step="0.01" value="1.2" inputmode="decimal" /><small>PUE es una razón energética; usarla aquí sobre potencia supone que representa este punto de operación.</small></div><div class="s5-tool-field"><label for="s5-dc-res-es">Reserva de capacidad IT <span>%</span></label><input id="s5-dc-res-es" data-field="facilityReservePct" type="number" min="0" max="95" step="1" value="10" inputmode="decimal" /><small>Margen que no se asigna a la carga calculada.</small></div></section>
<section class="s5-tool-controls__section"><h2>Racks</h2><div class="s5-tool-field"><label for="s5-dc-racks-es">Racks disponibles <span>unidades</span></label><input id="s5-dc-racks-es" data-field="racks" type="number" min="1" step="1" value="200" inputmode="numeric" /></div><div class="s5-tool-field"><label for="s5-dc-installed-es">Aceleradores instalados por rack <span>unidades</span></label><input id="s5-dc-installed-es" data-field="installedPerRack" type="number" min="1" step="1" value="64" inputmode="numeric" /></div><div class="s5-tool-field"><label for="s5-dc-rack-power-es">Límite eléctrico IT por rack <span>kW</span></label><input id="s5-dc-rack-power-es" data-field="rackPowerKW" type="number" min="0.1" step="1" value="60" inputmode="decimal" /></div><div class="s5-tool-field"><label for="s5-dc-rack-cooling-es">Capacidad de retirar calor IT por rack <span>kW</span></label><input id="s5-dc-rack-cooling-es" data-field="rackCoolingKW" type="number" min="0.1" step="1" value="50" inputmode="decimal" /><small>Usa el límite térmico efectivo del rack o del sistema de refrigeración que lo sirve.</small></div></section>
<section class="s5-tool-controls__section"><h2>Hardware y cómputo</h2><div class="s5-tool-field"><label for="s5-dc-preset-es">Acelerador</label><select id="s5-dc-preset-es" data-field="preset"></select><small data-output="hardware-note">—</small></div><div class="s5-tool-field"><label for="s5-dc-power-es">Potencia media del acelerador <span>% del TDP</span></label><input id="s5-dc-power-es" data-field="powerUtilizationPct" type="number" min="0.1" max="100" step="1" value="85" inputmode="decimal" /></div><div class="s5-tool-field"><label for="s5-dc-other-es">Resto de IT asociado <span>% sobre potencia de aceleradores</span></label><input id="s5-dc-other-es" data-field="otherITPct" type="number" min="0" max="1000" step="1" value="15" inputmode="decimal" /><small>CPU, memoria, red y almacenamiento aproximados por acelerador.</small></div><div class="s5-tool-field"><label for="s5-dc-mfu-es">MFU de entrenamiento <span>% del pico denso</span></label><input id="s5-dc-mfu-es" data-field="mfuPct" type="number" min="0.1" max="100" step="1" value="45" inputmode="decimal" /></div></section>
<section class="s5-tool-controls__section"><h2>Mapa opcional a inferencia</h2><div class="s5-tool-field"><label for="s5-dc-toks-es">Throughput sostenido medido <span>tokens de salida/s por acelerador</span></label><input id="s5-dc-toks-es" data-field="measuredTokensPerSecPerAccelerator" type="number" min="0" step="10" value="0" inputmode="decimal" /><small>0 desactiva la estimación. Introduce una medición de tu modelo, runtime, batch y SLO; no se infiere desde FLOPs.</small></div><div class="s5-tool-field"><label for="s5-dc-out-es">Salida media por finalización <span>tokens</span></label><input id="s5-dc-out-es" data-field="avgOutputTokens" type="number" min="1" step="10" value="500" inputmode="decimal" /></div></section>
<details><summary>Supuestos avanzados del acelerador</summary><section class="s5-tool-controls__section"><div class="s5-tool-field"><label for="s5-dc-peak-es">Pico BF16 denso <span>TFLOP/s</span></label><input id="s5-dc-peak-es" data-field="peakTflops" type="number" min="0.001" step="1" value="989.5" inputmode="decimal" /></div><div class="s5-tool-field"><label for="s5-dc-tdp-es">TDP máximo <span>W</span></label><input id="s5-dc-tdp-es" data-field="tdpW" type="number" min="1" max="5000" step="10" value="700" inputmode="decimal" /></div></section></details>
<section class="s5-tool-controls__section"><div class="s5-tool-actions"><button class="s5-tool-action" type="button" data-action="share">Copiar escenario</button><button class="s5-tool-action" type="button" data-action="json">Exportar JSON</button><button class="s5-tool-action" type="button" data-action="reset">Restablecer</button></div><p class="s5-tool-feedback" data-s5-tool-feedback hidden aria-live="polite"></p></section>
</form>

<section class="s5-tool-results">
<div class="s5-section-head s5-section-head--with-copy"><div><div class="s5-eyebrow">Resultado</div><h2>La capacidad es el mínimo entre límites independientes.</h2></div><p data-output="interpretation" aria-live="polite">—</p></div>
<div class="s5-datacenter-capacity-kpis"><div><small>Aceleradores activos</small><strong data-output="active-accelerators">—</strong><span>máximo simultáneo</span></div><div><small>Cuello de botella</small><strong data-output="bottleneck">—</strong><span>límite que gana</span></div><div><small>Potencia de instalación</small><strong data-output="facility-draw">—</strong><span>con PUE aplicado</span></div><div><small>Cómputo de entrenamiento</small><strong data-output="training-throughput">—</strong><span>pico denso × MFU</span></div></div>
<section class="s5-dc-panel"><div class="s5-dc-panel__head"><h3>Cuatro límites sobre la misma flota</h3><p>Cada barra muestra cuántos aceleradores admitiría ese límite por separado. El número publicable es el menor. Así no se confunde potencia disponible con espacio físico o refrigeración suficiente.</p></div><div class="s5-dc-constraints" data-output="constraint-bars"></div></section>
<div class="s5-dc-detail-grid"><section><h3>Instalación</h3><p>Capacidad IT utilizable: <strong data-output="usable-it">—</strong></p><p>Reserva IT: <strong data-output="reserved-it">—</strong></p><p>Margen de potencia total: <strong data-output="facility-headroom">—</strong></p><p>Uso de la envolvente total: <strong data-output="facility-utilization">—</strong></p></section><section><h3>Rack</h3><p>Máximo activo por rack: <strong data-output="max-per-rack">—</strong></p><p>Carga IT a ese máximo: <strong data-output="rack-it">—</strong></p><p>Margen eléctrico por rack: <strong data-output="rack-power-headroom">—</strong></p><p>Margen térmico por rack: <strong data-output="rack-cooling-headroom">—</strong></p></section><section><h3>Entrenamiento</h3><p>Pico BF16 denso de la flota activa: <strong data-output="peak-compute">—</strong></p><p>Cómputo sostenido con MFU: <strong data-output="training-throughput">—</strong></p><p>Cómputo sostenido por día: <strong data-output="training-day">—</strong></p></section><section><h3>Densidad física</h3><p>Slots instalados realmente utilizables: <strong data-output="slot-utilization">—</strong></p><p>Una baja utilización aquí no implica mala eficiencia: puede indicar que potencia o refrigeración limitan antes que el espacio físico.</p></section></div>
<section class="s5-dc-inference"><h3>Inferencia: usa una medición de serving, no el pico de FLOPs</h3><p data-output="inference-note">—</p><div class="s5-dc-inference__metrics"><div><small>Throughput agregado</small><strong data-output="inference-tokens">—</strong></div><div><small>Finalizaciones aproximadas</small><strong data-output="inference-completions">—</strong></div></div></section>
</section></div>

<section class="s5-section"><div class="s5-section-head"><div><div class="s5-eyebrow">Método</div><h2>Separa instalación, rack y servicio.</h2></div></div><div class="s5-dc-method"><div><strong>1 · Instalación</strong><p>La potencia total se divide por un PUE representativo para aproximar la capacidad IT. Después se retira la reserva operativa.</p></div><div><strong>2 · Rack</strong><p>Cada acelerador suma potencia media y resto de IT. Ese footprint se contrasta por separado con slots instalados, límite eléctrico y capacidad térmica del rack.</p></div><div><strong>3 · Cómputo y serving</strong><p>Entrenamiento usa pico BF16 denso × MFU. Inferencia solo se calcula cuando introduces throughput sostenido medido en tu stack; no se transforma FLOPs en tokens/s.</p></div></div></section>
<section class="s5-section"><div class="s5-note-feature"><div><div class="s5-eyebrow">Límites</div><h2>Es un modelo de capacidad, no un diseño MEP ni un benchmark de serving.</h2><p>PUE es una razón energética y puede cambiar con carga y clima. TDP no equivale a consumo medio. La aproximación del resto de IT es lineal aunque CPU, red y almacenamiento no escalen siempre así. La capacidad térmica debe venir del diseño real del rack y su sistema de refrigeración. MFU depende del workload y del software. El throughput de inferencia depende del modelo, precisión, contexto, batching, runtime y SLO; por eso esta herramienta solo lo agrega cuando aportas una medición por acelerador.</p><p><a href="/herramientas/computo-energia-entrenamiento/">Comparar con el estimador de cómputo y energía de entrenamiento →</a></p></div><div class="s5-note-feature__meta"><a href="https://www.nvidia.com/en-us/data-center/h100/">NVIDIA H100</a><br /><a href="https://www.nvidia.com/en-us/data-center/h200/">NVIDIA H200</a><br /><a href="https://www.nvidia.com/en-us/data-center/hgx/">NVIDIA HGX B200</a><br /><a href="https://docs.nvidia.com/dgx/dgxb200-user-guide/introduction-to-dgxb200.html">DGX B200 · potencia</a><br /><a href="https://docs.nvidia.com/dgx-pdf/nvidia-dgx-superpod-data-center-best-practices-with-dgx-b200.pdf">DGX B200 · rack</a><br /><a href="https://www.thegreengrid.org/node/372">The Green Grid · PUE</a><br />Fuentes revisadas: 22-08-2026</div></div></section>
</div>